400 kVA – 800 kVA Threephase Online UPS Uninterruptible Power Supply

In stock

• Reverse Current Protection
• High reliability
• Selectable output
• Online Design / Double Conversion
• Parallelizable up to N+1
• Automatic Voltage Regulation Function
• Wide Input Voltage Range
• Pure Sine Wave Output
• Built-in DC start function (Cold Start)
• Automatic startup during AC recovery
• Replaceable Battery Design
• 50/60 Hz Frequency auto-sensing
• Lightning and Overcurrent Protection
• Bottom Discharge Protection
• Battery Low, Overload Alarm



Download Product Catalog

Product details

400 kVA – 800 kVA Three-Phase Online UPS

Three-phase Online UPS with 400 kVA – 800 kVA capacity are professional power solutions designed for the critical energy needs of small and medium-scale enterprises. These systems offer maximum performance in areas requiring uninterrupted power such as data centers, hospitals, industrial facilities, and office buildings.

Uninterrupted Energy Assurance for Your Business with Three-Phase Online UPS

Three-Phase Online UPS systems ranging from 400 kVA to 800 kVA, developed for the critical energy needs of small, medium and large-scale enterprises, secure your business continuity. They provide complete protection against problems such as power outages, fluctuations, and voltage irregularities, protecting your equipment and data in sensitive environments such as data centers, hospitals, industrial facilities, and office buildings.

What is Three-Phase Online UPS?

Three-phase Online UPS systems provide uninterrupted energy in critical infrastructures such as data centers, hospitals, industrial facilities, and office buildings. They offer clean and stable power even during power outages, voltage fluctuations, and harmonic distortions.

Three-Phase Uninterruptible Power Supply Suitable for Your Needs

With a wide capacity range specially designed for systems of different sizes, you can easily find the most suitable solution for your business.

400 kVA – 500 kVA UPS: Designed for facilities with high power density such as large-scale industrial complexes, enterprise data centers, and comprehensive hospital campuses. Offers maximum efficiency and business continuity by managing the energy infrastructure of all critical operations from a single center.
600 kVA – 800 kVA UPS: The cornerstone of mega projects requiring the highest power capacity with zero interruption tolerance. Provides the highest level of power assurance and performance for hyperscale data centers, giant production facilities, international airports, and critical infrastructures for national networks.

Why Should You Choose Three-Phase (Three-Phase) Online UPS?

  • Ensures business continuity with uninterrupted energy.
  • Helps you save energy with high efficiency.
  • Keeps your equipment safe with powerful protection features.
  • Offers customized solutions for your needs with flexible capacity options.

Three-Phase UPS Usage Areas

Offers a reliable solution in every area where uninterrupted and clean energy is vital:

  • Data Centers and Server Rooms
  • Hospitals, Operating Rooms, and Medical Imaging Devices
  • Industrial Production Facilities and Automation Systems
  • Telecommunications Infrastructures
  • Financial Institutions and Banking Systems
  • Transportation and Traffic Control Centers

Technical Information

Download Catalog SheetHE Series Threephase Online UPS 400 kVA – 800 kVA
MODELHE404HE504HE604HE804
Capacity400kVA / 320kW500kVA / 400kW600kVA / 480kW800kVA / 640kW
GENERAL
UPS TypeTower Type
TechnologyTrue Online Double Conversion
Standart FeaturesOver Load, Over Temprature, Surge Protections
Smart FeaturesCold Start, AC Restart; Auto Restart; Auto Test
CoolingSmart Air Cooling
CommunicationRS232, USB / Dry Contacts, EPO, SNMP (Optional)
INPUT
Voltage380-400-415 VAC (Selectable)
Input Voltage Range± 25%
Frequency50 or 60 Hz (Selectable)
THDi≤ 3% @ 205-245VAC
OUTPUT
Voltage380-400-415 VAC (Same as Input)
Frequency50 or 60 Hz (Selectable)
Power Factor0.8
Wave FormPure Sine Wave
THDv≤ 3 % THD (Linear Load); ≤ 5 % THD (Non-linear Load)
Crest Factor3:1
Overload Capability100% ~ 110%: 10min; 110% ~ 130%: 1min; >130% : 1sec
EFFICIENCY
Overal Efficiency≥95% @ 100% Rated Load
ECO Mode Efficiency≥98% @ 100% Rated Load
BATTERY
TypeVRLA AGM
DC Voltage12 VDC/ each; Total Requirement is 720 VDC
Quantity120 Pcs240 Pcs
Capacity65 Ah80 Ah100 Ah65 Ah
Recharge Period6-8 Hours Recover to 90% Capacity
ENVIRONMENT
Operating Temprature Range0-40 °C
Storage Temprature0-70 °C
Relative Humidity Range20%-90% Non-Condensing
OutletTerminals (3P+ N+ G)
AVR FeatureYes
Audible Noise<75dBA<70dBA
DIMENSIONS & WEIGHT
Battery Pack Dimensions2 Pcs x 1774x560x17814 Pcs x 1774x560x1781
Dimensions (W*D*H) (mm)1600x870x18002190x810x20303220x870x1800
Net Weight (Kg)240250380400
Gross Weight (Kg)254265403424
Back to Top