100 kVA – 300 kVA Threephase Online UPS Uninterruptible Power Supply

In stock

• Reverse Current Protection
• High reliability
• Selectable output
• Online Design / Double Conversion
• Parallelizable up to N+1
• Automatic Voltage Regulation Function
• Wide Input Voltage Range
• Pure Sine Wave Output
• Built-in DC start function (Cold Start)
• Automatic startup during AC recovery
• Replaceable Battery Design
• 50/60 Hz Frequency auto-sensing
• Lightning and Overcurrent Protection
• Bottom Discharge Protection
• Battery Low, Overload Alarm



Download Product Catalog

Product details

100 kVA – 300 kVA Three-Phase Online UPS

Three-phase Online UPS with 100 kVA – 300 kVA capacity are professional power solutions designed for the critical energy needs of small and medium-scale enterprises. These systems offer maximum performance in areas requiring uninterrupted power such as data centers, hospitals, industrial facilities, and office buildings.

Uninterrupted Energy Assurance for Your Business with Three-Phase Online UPS

Three-Phase Online UPS systems ranging from 100 kVA to 300 kVA, developed for the critical energy needs of small, medium and large-scale enterprises, secure your business continuity. They provide complete protection against problems such as power outages, fluctuations, and voltage irregularities, protecting your equipment and data in sensitive environments such as data centers, hospitals, industrial facilities, and office buildings.

What is Three-Phase Online UPS?

Three-phase Online UPS systems provide uninterrupted energy in critical infrastructures such as data centers, hospitals, industrial facilities, and office buildings. They offer clean and stable power even during power outages, voltage fluctuations, and harmonic distortions.

Three-Phase Uninterruptible Power Supply Suitable for Your Needs

With a wide capacity range specially designed for systems of different sizes, you can easily find the most suitable solution for your business.

100 kVA – 120 kVA UPS: Forms the energy backbone of medium and large-scale enterprises. Provides a high-efficiency, ideal protection for large office buildings, hospital imaging (MRI, CT) and life support units, medium-sized data centers, and industrial facilities.
160 kVA – 200 kVA UPS: Designed for critical applications with higher energy needs. Offers a powerful and uninterrupted energy infrastructure for large data centers, telecommunication exchanges, industrial automation systems, and production lines with no tolerance for interruption.
250 kVA – 300 kVA UPS: The top-level solution for large-scale operations with the highest power demands. Securely meets the entire energy needs of financial institutions’ transaction centers, large production campuses, cloud computing infrastructures, and facilities of strategic importance.

Why Should You Choose Three-Phase (Three-Phase) Online UPS?

  • Ensures business continuity with uninterrupted energy.
  • Helps you save energy with high efficiency.
  • Keeps your equipment safe with powerful protection features.
  • Offers customized solutions for your needs with flexible capacity options.

Three-Phase UPS Usage Areas

Offers a reliable solution in every area where uninterrupted and clean energy is vital:

  • Data Centers and Server Rooms
  • Hospitals, Operating Rooms, and Medical Imaging Devices
  • Industrial Production Facilities and Automation Systems
  • Telecommunications Infrastructures
  • Financial Institutions and Banking Systems
  • Transportation and Traffic Control Centers

Technical Information

Download Catalog SheetHE Series Threephase UPS 100 kVA – 300 kVA
MODELHE104HE124HE164HE204HE254HE304
Capacity100kVA / 80kW120kVA / 96kW160kVA / 128kW200kVA / 160kW250kVA / 200kW300kVA / 240kW
GENEL
UPS TypeTower Type
TechnologyTrue Online Double Conversion
Standart FeaturesOver Load, Over Temprature, Surge Protections
Smart FeaturesCold Start, AC Restart; Auto Restart; Auto Test
CoolingSmart Air Cooling
CommunicationRS232, USB / Dry Contacts, EPO, SNMP (Optional)
INPUT
Voltage380-400-415 VAC (Selectable)
Input Voltage Range± 25%
Frequency50 or 60 Hz (Selectable)
THDi≤ 3% @ 205-245VAC
OUTPUT
Voltage380-400-415 VAC (Same as Input)
Frequency50 or 60 Hz (Selectable)
Power Factor0.8
Wave FormPure Sine Wave
THDv≤ 3 % THD (Linear Load); ≤ 5 % THD (Non-linear Load)
Crest Factor3:1
Overload Capability100% ~ 110%: 10min; 110% ~ 130%: 1min; >130% : 1sec
EFFICIENCY
Overal Efficiency≥95% @ 100% Rated Load
ECO Mode Efficiency≥98% @ 100% Rated Load
BATTERY
TypeVRLA AGM
DC Voltage12 VDC/ each; Total Requirement is 720 VDC
Quantity120 Pcs60 Pcs
Capacity18 Ah40 Ah55 Ah65 Ah80 Ah100 Ah
Recharge Period6-8 Hours Recover to 90% Capacity
ENVIRONMENT
Operating Temprature Range0-40 °C
Storage Temprature0-70 °C
Relative Humidity Range20%-90% Non-Condensing
OutletTerminals (3P+ N+ G)
AVR FeatureYes
Audible Noise<65dBA<70dBA<75dBA
DIMENSIONS & WEIGHT
Battery Pack Dimensions2 Pcs x 926x386x8462 Pcs x 1566x386x1166
Dimensions (W*D*H) (mm)550x800x1340680x1010x1750780x1260x1900
Net Weight (Kg)240250380400820850
Gross Weight (Kg)254265403424869901
Back to Top