10 kVA – 120 kVA Threephase Online UPS Uninterruptible Power Supply

In stock

• Online Design / Double Conversion
• Parallelizable up to N+1
• Automatic Voltage Regulation Function
• Built-in DC start function (Cold Start)
• Automatic startup during AC recovery
• Replaceable Battery Design
• Overcurrent and Load Protection
• Bottom Discharge Protection



Download Product Catalog

Product details

10 kVA – 120 kVA Three-Phase Online UPS

Three-phase Online UPS with 10 kVA – 120 kVA capacity are professional power solutions designed for the critical energy needs of small and medium-scale enterprises. These systems offer maximum performance in areas requiring uninterrupted power such as data centers, hospitals, industrial facilities, and office buildings.

Uninterrupted Energy Assurance for Your Business with Three-Phase Online UPS

Three-Phase Online UPS systems ranging from 10 kVA to 120 kVA, developed for the critical energy needs of small, medium and large-scale enterprises, secure your business continuity. They provide complete protection against problems such as power outages, fluctuations, and voltage irregularities, protecting your equipment and data in sensitive environments such as data centers, hospitals, industrial facilities, and office buildings.

What is Three-Phase Online UPS?

Three-phase Online UPS systems provide uninterrupted energy in critical infrastructures such as data centers, hospitals, industrial facilities, and office buildings. They offer clean and stable power even during power outages, voltage fluctuations, and harmonic distortions.

Three-Phase Uninterruptible Power Supply Suitable for Your Needs

With a wide capacity range specially designed for systems of different sizes, you can easily find the most suitable solution for your business.

10 kVA – 20 kVA UPS: Ideal for small and medium-scale offices, laboratories, and small server rooms.
30 kVA – 40 kVA UPS: Offers high efficiency for growing data centers, medium-scale production lines, and critical infrastructures.
60 kVA – 80 kVA UPS: Designed for systems with high energy requirements such as large-scale enterprises, hospital imaging devices, and industrial facilities.
100 kVA – 120 kVA UPS: Provides maximum power capacity and reliability for the largest data centers, industrial automation systems, and critical facilities with no tolerance for interruption.

Why Should You Choose Three-Phase (Three-Phase) Online UPS?

Ensures business continuity with uninterrupted energy.
Helps you save energy with high efficiency.
Keeps your equipment safe with powerful protection features.
Offers customized solutions for your needs with flexible capacity options.

Three-Phase UPS Usage Areas

Offers a reliable solution in every area where uninterrupted and clean energy is vital:

  • Data Centers and Server Rooms
  • Hospitals, Operating Rooms, and Medical Imaging Devices
  • Industrial Production Facilities and Automation Systems
  • Telecommunications Infrastructures
  • Financial Institutions and Banking Systems
  • Transportation and Traffic Control Centers

Technical Information

Katalog Föyünü İndirHES Serisi Threephase Online UPS 10 kVA – 120 kVA
MODELHES103HES153HES203HES303HES403HES603HES803HES104HES124
Capacity10kVA / 10 kW15kVA / 15 kW20kVA / 20 kW30kVA / 30 kW40kVA / 40 kW60kVA / 60 kW80kVA / 80 kW100kVA / 100 kW120kVA / 120 kW
GENERAL
Technology3-Level, Double conversation Online VFI-SS-111
WaveformSinusoidal
ArchitectureStand Alone or Optional Parallel
INPUT
Input Voltage380, 400, 415 V 3Ph+N+PE
Input Frequency45-65 Hz
Voltage Tolerance (%100 load)(-20)% (+20)%
Voltage Tolerance (%50 load)(-36)% (+20)%
Input Power Factor0,99
Input Current Harmonic3%
OUTPUT< 0.01 msn
Output Voltage380, 400, 415 V 3Ph+N+PE
Output Voltage Tolerance±1%
Overall Eciency* (AC-AC)Up to 96% (Half load)
Crest FactorUp to 98% (Optional)
Ecomode Eciency50/ 60Hz +0,01 free run (Adjustable from LCD Panel)
Nominal Output Frequency3:1
Output Power Factor1.0
THD of Output Voltage2% (Linear load) & 5% (Non-linear load)
BATTERIES3:1
Battery TypeVRLA-AGM / GEL / NiCd / Li-ion
Battery TestAutomatic or Manual
Battery Charge Time<6h-8h
COMMUNICATION AND MANAGEMENT
LCD DisplayGraphical Icd screen, Led bar status
Communication Ports
(Optional)
RS485, Genset, SNMP, GSM Modem, Relay Contacts, Input Contacts, Modbus and USB
Battery Temperature Sensor ContactAvailable
Emergency Power O (Epo)Available
Accessories (Optional)Galvanic Isolation Transformer, Remote Monitoring Panel
CHARGER CAPACITY
Maximum4A (13A optional)13A
Higher capacity
charge card option
Available
BATTERY QUANTITY
With Internal Battery (12V)20 - 32 pcs 7/9Ah32 pcs 7/9Ah32 pcs 7/9Ah2x30 pcs 7/9Ah2x30 pcs 7/9Ah40 pcs 12/18Ah40 pcs 12/18Ah
External Cabinet with 4A Charger OptionV1: 30 - 40 pcs (Default 30 pcs)
V2: 40 - 46 pcs (Default 40 pcs)
Default 40 pcs
External Cabinet with 13A Charger Option30 - 46 pcs (Default 30 pcs - Adjustable from LCD Panel)40-46 pcs (Default 40 pcs - Adjustable from LCD Panel)
DIMENSIONS
Dimensions W*D*H (mm)305*735*855325*895*1078432*930*1257
Net Weight (kg)485154657195115125130
AMBIENT CONDITIONS
Operating temperature (°C)0°C - 40°C
StorageTempature-15°C/+ 55°C
Proposed Temp. to Extend Battery Life20 - 25°C
Relative Humidity (%)< 95% not condensing
Altittude< 1500m<60 dBA
Noise (at 1 meter)<55 dBA<60 dBA
Protection ClassIP20 (Higher IP Ratings are optional)
COMPLIANCE
Referance Product
Standards
EN 62040-1 (Safety), EN 62040-2 (EMC), EN 62040-3 (Performance)
Back to Top